As part of the service we offer our clients, Professional Lighting Design Limited follow best practise methods and guidelines issued by the Charted Institute of Building Services Engineers, the Institute of Lighting Professional and the Professional Lighting Design Association.
Regarding the project Kestrel Insurance, Main Road, Onchan below are the two relevant tables of information.
Lighting Classification
The table below (1.1) is produced by the Institution of Lighting Professionals and is contained with their Guidance Notes for the Reduction of Light Pollution, 2000. This demonstrates the parameters for identifying and understanding an identified area as an Environmental Zone.
Lighting Technical Parameters for Signs
The table below (1.2) is identifies the recommended limits for the average luminance for self-luminance signs, as published by the Institution of Lighting Professionals.
Table 1.1 Environmental Zones
Zone
Surrounding
Lighting Environment
Examples
E0
Protected
Dark
UNESCO Starlight Reserves, IDA Dark Sky Parks
E1
Natural
Intrinsically dark
National Parks, Areas of Outstanding Natural Beauty etc
E2
Rural
Low district brightness
Village or relatively dark outer suburban locations
E3
Suburban
Medium district brightness
Small town centres or suburban locations
E4
Urban
High district brightness
Town/city centres with high levels of night-time activity
Table 1.2 Luminance limits for illuminated signs
Light Technical Parameter
Application Conditions
Environmental Zones
E1
E2
E3
E4
Sign Luminance (Ls)
Taken as the product of the design average illuminance and reflectance factor divided by π, or for self-luminous signs the average luminance.
50 cd/m²
400 cd/m²
800 cd/m²
1000 cd/m²